| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| GE Fanuc Proficy Real-Time Information Portal 2.6 and earlier uses HTTP Basic Authentication, which transmits usernames and passwords in base64-encoded cleartext and allows remote attackers to steal the passwords and gain privileges. |
| Cross-site scripting (XSS) vulnerability in GE Multilink ML810/3000/3100 series switch 5.2.0 and earlier, and GE Multilink ML800/1200/1600/2400 4.2.1 and earlier. |
| GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier use the same RSA private key across different customers' installations, which makes it easier for remote attackers to obtain the cleartext content of network traffic by reading this key from a firmware image and then sniffing the network. |
| GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier allow remote attackers to cause a denial of service (resource consumption or reboot) via crafted packets. |
| The 17046 Ethernet card before 94450214LFMT100SEM-L.R3-CL for the GE Digital Energy Hydran M2 does not properly generate random values for TCP Initial Sequence Numbers (ISNs), which makes it easier for remote attackers to spoof packets by predicting these values. |
| The (1) CimView and (2) CimEdit components in GE Proficy HMI/SCADA-CIMPLICITY 8.2 and earlier allow remote attackers to gain privileges via a crafted CIMPLICITY screen (aka .CIM) file. |
| The CIMPLICITY Web-based access component, CimWebServer, does not check
the location of shell files being loaded into the system. By modifying
the source location, an attacker could send shell code to the
CimWebServer which would deploy the nefarious files as part of any SCADA
project. This could allow the attacker to execute arbitrary code. |
| Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622. |
| A Stack-based Buffer Overflow issue was discovered in GE CIMPLICITY Versions 9.0 and prior. A function reads a packet to indicate the next packet length. The next packet length is not verified, allowing a buffer overwrite that could lead to an arbitrary remote code execution. |
| A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware versions prior to Version 5.23; SR 489 Generator Protection Relay, firmware versions prior to Version 4.06; SR 745 Transformer Protection Relay, firmware versions prior to Version 5.23; SR 369 Motor Protection Relay, all firmware versions; Multilin Universal Relay, firmware Version 6.0 and prior versions; and Multilin URplus (D90, C90, B95), all versions. Ciphertext versions of user passwords were created with a non-random initialization vector leaving them susceptible to dictionary attacks. Ciphertext of user passwords can be obtained from the front LCD panel of affected products and through issued Modbus commands. |
| An issue was discovered in General Electric (GE) Proficy HMI/SCADA iFIX Version 5.8 SIM 13 and prior versions, Proficy HMI/SCADA CIMPLICITY Version 9.0 and prior versions, and Proficy Historian Version 6.0 and prior versions. An attacker may be able to retrieve user passwords if he or she has access to an authenticated session. |
| GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR. |
| A vulnerability classified as critical was found in GE Voluson S8. Affected is the underlying Windows XP operating system. Missing patches might introduce an excessive attack surface. Access to the local network is required for this attack to succeed. |
| A code injection vulnerability exists in one of the webpages in GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06 that could allow an authenticated remote attacker to execute arbitrary code on the system. |
| By having access to the hard-coded cryptographic key for GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06, attackers would be able to intercept and decrypt encrypted traffic through an HTTPS connection. |
| GE UR firmware versions prior to version 8.1x supports web interface with read-only access. The device fails to properly validate user input, making it possible to perform cross-site scripting attacks, which may be used to send a malicious script. Also, UR Firmware web server does not perform HTML encoding of user-supplied strings. |
| GE UR firmware versions prior to version 8.1x web server task does not properly handle receipt of unsupported HTTP verbs, resulting in the web server becoming temporarily unresponsive after receiving a series of unsupported HTTP requests. When unresponsive, the web server is inaccessible. By itself, this is not particularly significant as the relay remains effective in all other functionality and communication channels. |
| GE UR firmware versions prior to version 8.1x shares MODBUS memory map as part of the communications guide. GE was made aware a “Last-key pressed” MODBUS register can be used to gain unauthorized information. |
| GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The weakness is assessed, and mitigation is implemented in firmware Version 8.10. |
| GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user. |