CVE-2024-54678 1 Siemens 13 Simatic Pcs Neo, Simatic S7-plcsim, Simatic Step 7 and 10 more 2026-10-13 8.2 High
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SIMATIC PCS neo V6.0 (All versions < V6.0 SP1 Update 1), SIMATIC S7-PLCSIM V17 (All versions), SIMATIC STEP 7 V17 (All versions < V17 Update 9), SIMATIC STEP 7 V18 (All versions < V18 Update 6), SIMATIC STEP 7 V19 (All versions < V19 Update 4), SIMATIC STEP 7 V20 (All versions < V20 Update 4), SIMATIC WinCC V17 (All versions < V17 Update 9), SIMATIC WinCC V18 (All versions < V18 Update 6), SIMATIC WinCC V19 (All versions < V19 Update 4), SIMATIC WinCC V20 (All versions < V20 Update 4), SIMOCODE ES V17 (All versions), SIMOCODE ES V18 (All versions), SIMOCODE ES V19 (All versions), SIMOCODE ES V20 (All versions), SIMOTION SCOUT TIA V5.4 (All versions), SIMOTION SCOUT TIA V5.5 (All versions), SIMOTION SCOUT TIA V5.6 (All versions < V5.6 SP1 HF7), SIMOTION SCOUT TIA V5.7 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SINAMICS Startdrive V19 (All versions), SINAMICS Startdrive V20 (All versions), SIRIUS Safety ES V17 (TIA Portal) (All versions), SIRIUS Safety ES V18 (TIA Portal) (All versions), SIRIUS Safety ES V19 (TIA Portal) (All versions), SIRIUS Safety ES V20 (TIA Portal) (All versions), SIRIUS Soft Starter ES V17 (TIA Portal) (All versions), SIRIUS Soft Starter ES V18 (TIA Portal) (All versions), SIRIUS Soft Starter ES V19 (TIA Portal) (All versions), SIRIUS Soft Starter ES V20 (TIA Portal) (All versions), TIA Portal Cloud V17 (All versions), TIA Portal Cloud V18 (All versions < V6.3.0.2), TIA Portal Cloud V19 (All versions < V5.2.1.1), TIA Portal Cloud V20 (All versions < V5.2.2.2), TIA Portal Test Suite V20 (All versions < V20 Update 4). Affected products do not properly sanitize Interprocess Communication input received through a Windows Named Pipe accessible to all local users. This could allow an authenticated local attacker to cause a type confusion and execute arbitrary code within the affected application.
CVE-2019-6568 1 Siemens 100 Cp1604, Cp1604 Firmware, Cp1616 and 97 more 2026-06-03 7.5 High
The webserver of the affected devices contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the device.
CVE-2020-15782 1 Siemens 63 6es7510-1dj01-0ab0, 6es7510-1sj01-0ab0, 6es7511-1ak01-0ab0 and 60 more 2026-06-02 9.8 Critical
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINAMICS PERFECT HARMONY GH180 Drives (Drives manufactured before 2021-08-13), SINUMERIK MC (All versions < V6.15), SINUMERIK ONE (All versions < V6.15). Affected devices are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks.
CVE-2025-40943 1 Siemens 90 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1507d Tf, Simatic Et 200sp Open Controller Cpu 1515sp Pc2 (incl. Siplus Variants) V2 Cpus - Windows Os and 87 more 2026-03-19 9.6 Critical
Affected devices do not properly sanitize contents of trace files. This could allow an attacker to inject code through social engineering an authorized user, who has the function right "Read diagnostics", to import a specially crafted trace file. The malicious trace file is insufficiently sanitized and malicious code could be executed in the clients browser session and trigger PLC operations via the webserver that the legitimate user is authorized to perform.
CVE-2022-30694 1 Siemens 223 6ag1151-8ab01-7ab0, 6ag1151-8ab01-7ab0 Firmware, 6ag1151-8fb01-2ab0 and 220 more 2025-04-21 6.5 Medium
The login endpoint /FormLogin in affected web services does not apply proper origin checking. This could allow authenticated remote attackers to track the activities of other users via a login cross-site request forgery attack.
CVE-2021-25675 1 Siemens 1 Simatic S7-plcsim 2024-11-21 5.5 Medium
A vulnerability has been identified in SIMATIC S7-PLCSIM V5.4 (All versions). An attacker with local access to the system could cause a Denial-of-Service condition in the application when it is used to open a specially crafted file. As a consequence, a divide by zero operation could occur and cause the application to terminate unexpectedly and must be restarted to restore the service.
CVE-2021-25674 1 Siemens 1 Simatic S7-plcsim 2024-11-21 5.5 Medium
A vulnerability has been identified in SIMATIC S7-PLCSIM V5.4 (All versions). An attacker with local access to the system could cause a Denial-of-Service condition in the application when it is used to open a specially crafted file. As a consequence, a NULL pointer deference condition could cause the application to terminate unexpectedly and must be restarted to restore the service.
CVE-2021-25673 1 Siemens 1 Simatic S7-plcsim 2024-11-21 5.5 Medium
A vulnerability has been identified in SIMATIC S7-PLCSIM V5.4 (All versions). An attacker with local access to the system could cause a Denial-of-Service condition in the application when it is used to open a specially crafted file. As a consequence, the application could enter an infinite loop, become unresponsive and must be restarted to restore the service.
CVE-2019-10929 1 Siemens 33 Simatic Cp 1626, Simatic Cp 1626 Firmware, Simatic Et 200sp Open Controller Cpu 1515sp Pc and 30 more 2024-11-21 5.9 Medium
A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.