| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. |
| Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. |
| An encryption vulnerability exists in all versions prior to V15.00.001 of Rockwell Automation FactoryTalk® AssetCentre. The vulnerability exists due to a weak encryption methodology and could allow a threat actor to extract passwords belonging to other users of the application. |
| A data exposure vulnerability exists in all versions prior to V15.00.001 of Rockwell Automation FactoryTalk® AssetCentre. The vulnerability exists due to storing credentials in the configuration file of EventLogAttachmentExtractor, ArchiveExtractor, LogCleanUp, or ArchiveLogCleanUp packages. |
| A data exposure vulnerability exists in all versions prior to V15.00.001 of Rockwell Automation FactoryTalk® AssetCentre. The vulnerability exists due to insecure storage of FactoryTalk® Security user tokens, which could allow a threat actor to steal a token and, impersonate another user. |
| An Improper Input Validation issue was discovered in Rockwell Automation FactoryTalk Alarms and Events, Version 2.90 and earlier. An unauthenticated attacker with remote access to a network with FactoryTalk Alarms and Events can send a specially crafted set of packets packet to Port 403/TCP (the history archiver service), causing the service to either stall or terminate. |
| The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authenticated attacker to decipher user credentials, including the Windows user or Windows DeskLock passwords. If the compromised user has an administrative account, an attacker could gain full access to the user’s operating system and certain components of FactoryTalk View SE. |
| Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials. |
| A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services. |
| Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine. |
| Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier components contain .NET remoting endpoints that deserialize untrusted data without sufficiently verifying that the resulting data will be valid. This vulnerability may allow a remote, unauthenticated attacker to gain full access to the FactoryTalk AssetCentre main server and all agent machines. |
| A deserialization vulnerability exists in how the AosService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre. |
| The ArchiveService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier exposes functions lacking proper authentication. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary SQL statements. |
| A vulnerability exists in the RunSearch function of SearchService service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier, which may allow for the execution of remote unauthenticated arbitrary SQL statements. |
| The AosService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier exposes functions lacking proper authentication. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary SQL statements. |
| Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier does not properly restrict all functions relating to IIS remoting services. This vulnerability may allow a remote, unauthenticated attacker to modify sensitive data in FactoryTalk AssetCentre. |
| A deserialization vulnerability exists in how the ArchiveService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre. |
| A deserialization vulnerability exists in how the LogService.rem service in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier verifies serialized data. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in FactoryTalk AssetCentre. |
| A vulnerability exists in the SaveConfigFile function of the RACompare Service, which may allow for OS command injection. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier. |
| SQL injection vulnerability in Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |